Table of Contents

Questions and Answers

  • M
    Melvin ClarkAug 17, 2025
    How to troubleshoot Siemens PXC-36 Compact Control Unit when analog input/output points are not reading as expected?
    • A
      austin49Aug 17, 2025
      If the analog input/output points on your Siemens Control Unit aren't reading correctly, verify that all slope/intercept entries are correct. Also, ensure the sensor is functioning properly and replace it if necessary.
  • C
    Cheryl RichardsonAug 19, 2025
    What to do if the RUN LED is off on Siemens PXC-36 Compact Control Unit?
    • J
      Jason DuranAug 19, 2025
      If the RUN LED is off on your Siemens Control Unit, first verify that power is connected. Then, check the service box and transformer ON switches. If power is ON, verify that the application firmware has booted. Finally, measure voltage on 24V~ and (Terminals 1 and 2).
  • W
    Walter SingletonAug 22, 2025
    How to fix Siemens Control Unit when points cannot be read or commanded from the operator's terminal?
    • B
      Beverly WarrenAug 22, 2025
      If points cannot be read or commanded from the operator's terminal on your Siemens Control Unit, verify that any failed points have been properly addressed. Also, verify the status of the points at the operator's terminal and ensure that points are not under Operator priority.
  • V
    vanessa13Aug 26, 2025
    What to do if the RUN LED is ON but no communication is possible with the HMI port on Siemens Control Unit?
    • R
      Ricardo LeeAug 26, 2025
      If the RUN LED is ON but there's no communication with the HMI port on your Siemens Control Unit, verify that the HMI port and your terminal are set to the same communication speed. Also, ensure that the cable from the field panel to the operator's terminal is properly connected at both ends. Open the enclosure and verify that both ends of the HMI extension cable are properly connected. Try unplugging the extension cable and plugging directly into the HMI port.
  • C
    Christopher TylerAug 27, 2025
    Why is there no communication over the ALN trunk on Siemens Control Unit?
    • R
      Robert MartinAug 28, 2025
      If there is no communication over the ALN trunk on your Siemens Control Unit, and the TX and RX LEDs are off or on solid, verify that the ALN trunk is securely connected to the ALN port on the Field Panel. On a two-wire ALN trunk, verify that the shield is connected to the enclosure ground and not the S-pin. Verify the field panel address and communication speed. Also, verify that the extended ALN trunk is operating.
  • T
    taylorsuzanneAug 30, 2025
    How to troubleshoot Siemens PXC-36 Compact Control Unit when LAI point does not function properly?
    • T
      Teresa JonesAug 30, 2025
      If an LAI point on your Siemens Control Unit isn't functioning correctly or shows as failed (*F*), verify that the field input device is within range. Also, make sure that points are properly terminated on the termination board or module. Confirm that the correct voltage is supplied to the device, as in a 4 to 20 mA device.
  • R
    Robert LewisSep 2, 2025
    How to troubleshoot Siemens PXC-36 Compact when LAO point does not function properly?
    • M
      michaelariasSep 2, 2025
      If an LAO point on your Siemens Control Unit is not functioning properly, displays as failed (*F*), and the output doesn't change when commanded, verify that the device connected to the point is functioning properly and is not shorted out. Also, verify that points are properly terminated on the termination board or module. Finally, verify that the correct voltage is supplied to the device.
  • D
    Donna BatesSep 5, 2025
    How do I fix no communication over the FLN trunk on Siemens Control Unit?
    • H
      Henry RodriguezSep 5, 2025
      If there is no communication over the FLN trunk on your Siemens Control Unit, verify the FLN address and communication speed. Also, verify the FLN trunk is connected to the correct FLN port.
  • J
    jonesmarkSep 7, 2025
    Why does the BATT LOW LED remain on after battery replacement in Siemens Control Unit?
    • P
      Paul VelasquezSep 7, 2025
      If the BATT LOW LED remains on after replacing the battery in your Siemens Control Unit, verify that the correct type of battery is being used. The LOW BATT LED remains ON if an alkaline battery is used in PXC Compact models with extended temperature range operation.
  • O
    ochoajonSep 12, 2025
    What to do if the battery low warning is displayed on Siemens Control Unit?
    • M
      Michael LewisSep 12, 2025
      If the BATT LOW LED is on or the battery low warning is displayed at the operator's terminal of your Siemens Control Unit, check that the mylar insert was removed from the AA (LR6) battery holder. Check for correct polarity (+ to +) and (- to -). Check that the battery is properly seated in the battery holder. If needed, replace the battery.

Summary

Compact Series Product Overview

Supported Point Types

Lists software-configurable and dedicated point types and configurations.

Hardware Features

Memory and Backup Batteries

Explains Flash ROM, RAM, AA, and coin cell battery functions.

Processor, Communication, and Electrical Specs

Covers processor, memory, communication interfaces, and electrical details.

PXM10 S;T Operator Display

Operator Display Menus and Navigation

Explains menu structure, navigation, login, logoff, and settings.

Alarms and Points Management

Details how to manage alarms and points via the operator display.

Point Monitor Application

Explains how to configure, display, and reset monitored points.

Service and Troubleshooting

Siemens PXC-36 Compact Specifications

General IconGeneral
BrandSiemens
ModelPXC-36 Compact
CategoryControl Unit
LanguageEnglish