EasyManua.ls Logo

Siemens PXC-16 Compact - User Manual

Siemens PXC-16 Compact
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
PXC Compact Series
Technical Reference Manual
145-172
Building Technologies
2018
-09-25 Restricted

Table of Contents

Questions and Answers

  • R
    Ronnie ZavalaAug 17, 2025
    How to troubleshoot Siemens PXC-16 Compact when analog input/output points are not reading as expected?
    • A
      Andrea FrancisAug 17, 2025
      If the analog input/output points on your Siemens Control Unit aren't reading correctly, verify that all slope/intercept entries are correct. Also, ensure the sensor is functioning properly and replace it if necessary.
  • B
    Billy RossAug 19, 2025
    What to do if the RUN LED is off on Siemens Control Unit?
    • D
      Darrell GentryAug 20, 2025
      If the RUN LED is off on your Siemens Control Unit, first verify that power is connected. Then, check the service box and transformer ON switches. If power is ON, verify that the application firmware has booted. Finally, measure voltage on 24V~ and (Terminals 1 and 2).
  • K
    Kevin TurnerAug 22, 2025
    How to fix Siemens Control Unit when points cannot be read or commanded from the operator's terminal?
    • M
      Matthew CarterAug 22, 2025
      If points cannot be read or commanded from the operator's terminal on your Siemens Control Unit, verify that any failed points have been properly addressed. Also, verify the status of the points at the operator's terminal and ensure that points are not under Operator priority.
  • R
    Regina WrightAug 25, 2025
    What to do if the RUN LED is ON but no communication is possible with the HMI port on Siemens PXC-16 Compact?
    • M
      Monique LeeAug 26, 2025
      If the RUN LED is ON but there's no communication with the HMI port on your Siemens Control Unit, verify that the HMI port and your terminal are set to the same communication speed. Also, ensure that the cable from the field panel to the operator's terminal is properly connected at both ends. Open the enclosure and verify that both ends of the HMI extension cable are properly connected. Try unplugging the extension cable and plugging directly into the HMI port.
  • M
    Michael CampbellAug 27, 2025
    Why is there no communication over the ALN trunk on Siemens PXC-16 Compact?
    • K
      Katelyn PetersonAug 27, 2025
      If there is no communication over the ALN trunk on your Siemens Control Unit, and the TX and RX LEDs are off or on solid, verify that the ALN trunk is securely connected to the ALN port on the Field Panel. On a two-wire ALN trunk, verify that the shield is connected to the enclosure ground and not the S-pin. Verify the field panel address and communication speed. Also, verify that the extended ALN trunk is operating.
  • R
    Randall SnowAug 30, 2025
    How to troubleshoot Siemens PXC-16 Compact when LAI point does not function properly?
    • S
      Sarah GrantAug 30, 2025
      If an LAI point on your Siemens Control Unit isn't functioning correctly or shows as failed (*F*), verify that the field input device is within range. Also, make sure that points are properly terminated on the termination board or module. Confirm that the correct voltage is supplied to the device, as in a 4 to 20 mA device.
  • J
    Julie StewartSep 2, 2025
    How to troubleshoot Siemens Control Unit when LAO point does not function properly?
    • A
      Alexandra PatrickSep 2, 2025
      If an LAO point on your Siemens Control Unit is not functioning properly, displays as failed (*F*), and the output doesn't change when commanded, verify that the device connected to the point is functioning properly and is not shorted out. Also, verify that points are properly terminated on the termination board or module. Finally, verify that the correct voltage is supplied to the device.
  • R
    Richard ReedSep 5, 2025
    How do I fix no communication over the FLN trunk on Siemens PXC-16 Compact?
    • C
      Christine McknightSep 5, 2025
      If there is no communication over the FLN trunk on your Siemens Control Unit, verify the FLN address and communication speed. Also, verify the FLN trunk is connected to the correct FLN port.
  • H
    heathertaylorSep 8, 2025
    Why does the BATT LOW LED remain on after battery replacement in Siemens Control Unit?
    • R
      Robin ShawSep 8, 2025
      If the BATT LOW LED remains on after replacing the battery in your Siemens Control Unit, verify that the correct type of battery is being used. The LOW BATT LED remains ON if an alkaline battery is used in PXC Compact models with extended temperature range operation.
  • C
    Cathy JacksonSep 12, 2025
    What to do if the battery low warning is displayed on Siemens PXC-16 Compact Control Unit?
    • A
      Alexandra BrownSep 12, 2025
      If the BATT LOW LED is on or the battery low warning is displayed at the operator's terminal of your Siemens Control Unit, check that the mylar insert was removed from the AA (LR6) battery holder. Check for correct polarity (+ to +) and (- to -). Check that the battery is properly seated in the battery holder. If needed, replace the battery.

Summary

Compact Series Product Overview

Compatibility and Protocol Support

Details compatibility with APOGEE, BACnet/IP, and TCP/IP protocols.

System Program, Licensing, and Points

Covers firmware, licensing, and supported point types.

Hardware Diagrams and Features

Shows diagrams for 16/24-point and 36-point models, plus hardware features.

Hardware Features

Memory, Backup, and Specifications

Explains memory types, battery backup, and general controller specifications.

Communication Interfaces and Ports

Details Ethernet, RS-485, USB, HMI, and TX-I/O ports.

PXC Compact on P1 Operation

Details PXC Compact operation in P1 mode, database structure, and applications.

HOA Upgrade Kits

Information on Hand-Off-Auto (HOA) upgrade kits for manual control.

PXM10 S;T Operator Display Modules

Overview, features, and specs of operator display modules.

Unitary Equipment Controller (UEC)

UEC features, specs, node modes (FLN, ALN), and limitations.

Smoke Control Application Requirements

Example ALN Configuration

Illustrates a typical ALN network setup for smoke control.

Service Information and Troubleshooting

General Service, ESD, and Battery Replacement

Covers service procedures, ESD precautions, and battery replacement.

Field Panel Troubleshooting

Diagnosing issues with points, LEDs, and communication.

TX-I;O Island Bus and Module Issues

Troubleshooting TX-I/O bus, LCD panels, and module replacement.

Siemens PXC-16 Compact Specifications

General IconGeneral
BrandSiemens
ModelPXC-16 Compact
CategoryControl Unit
LanguageEnglish

Related product manuals