PXC Compact Series
Technical Reference Manual
145-172
Building Technologies
2018
-09-25 Restricted

Table of Contents

Other manuals for Siemens PXC Compact Series

Questions and Answers

  • C
    Christine LutzAug 17, 2025
    How to troubleshoot Siemens PXC Compact when analog input/output points are not reading as expected?
    • M
      Mark WhiteAug 17, 2025
      If the analog input/output points on your Siemens Control Unit aren't reading correctly, verify that all slope/intercept entries are correct. Also, ensure the sensor is functioning properly and replace it if necessary.
  • R
    Richard CooperAug 20, 2025
    What to do if the RUN LED is off on Siemens Control Unit?
    • T
      tnorrisAug 20, 2025
      If the RUN LED is off on your Siemens Control Unit, first verify that power is connected. Then, check the service box and transformer ON switches. If power is ON, verify that the application firmware has booted. Finally, measure voltage on 24V~ and (Terminals 1 and 2).
  • R
    Robert SmithAug 23, 2025
    How to fix Siemens PXC Compact Control Unit when points cannot be read or commanded from the operator's terminal?
    • B
      bryangonzalezAug 23, 2025
      If points cannot be read or commanded from the operator's terminal on your Siemens Control Unit, verify that any failed points have been properly addressed. Also, verify the status of the points at the operator's terminal and ensure that points are not under Operator priority.
  • Y
    yweaverAug 26, 2025
    What to do if the RUN LED is ON but no communication is possible with the HMI port on Siemens Control Unit?
    • R
      Robert WestAug 26, 2025
      If the RUN LED is ON but there's no communication with the HMI port on your Siemens Control Unit, verify that the HMI port and your terminal are set to the same communication speed. Also, ensure that the cable from the field panel to the operator's terminal is properly connected at both ends. Open the enclosure and verify that both ends of the HMI extension cable are properly connected. Try unplugging the extension cable and plugging directly into the HMI port.
  • M
    martinezpamelaAug 28, 2025
    Why is there no communication over the ALN trunk on Siemens Control Unit?
    • D
      Dr. Larry Guerra DVMAug 28, 2025
      If there is no communication over the ALN trunk on your Siemens Control Unit, and the TX and RX LEDs are off or on solid, verify that the ALN trunk is securely connected to the ALN port on the Field Panel. On a two-wire ALN trunk, verify that the shield is connected to the enclosure ground and not the S-pin. Verify the field panel address and communication speed. Also, verify that the extended ALN trunk is operating.
  • M
    Melissa BeardAug 30, 2025
    How to troubleshoot Siemens Control Unit when LAI point does not function properly?
    • K
      katherine58Aug 30, 2025
      If an LAI point on your Siemens Control Unit isn't functioning correctly or shows as failed (*F*), verify that the field input device is within range. Also, make sure that points are properly terminated on the termination board or module. Confirm that the correct voltage is supplied to the device, as in a 4 to 20 mA device.
  • D
    Dennis MahoneySep 3, 2025
    How to troubleshoot Siemens PXC Compact Control Unit when LAO point does not function properly?
    • A
      Anne GonzalezSep 3, 2025
      If an LAO point on your Siemens Control Unit is not functioning properly, displays as failed (*F*), and the output doesn't change when commanded, verify that the device connected to the point is functioning properly and is not shorted out. Also, verify that points are properly terminated on the termination board or module. Finally, verify that the correct voltage is supplied to the device.
  • H
    hicksdavidSep 5, 2025
    How do I fix no communication over the FLN trunk on Siemens PXC Compact?
    • T
      Thomas JensenSep 5, 2025
      If there is no communication over the FLN trunk on your Siemens Control Unit, verify the FLN address and communication speed. Also, verify the FLN trunk is connected to the correct FLN port.
  • K
    Kerry ClarkSep 8, 2025
    Why does the BATT LOW LED remain on after battery replacement in Siemens Control Unit?
    • A
      Anthony MilesSep 8, 2025
      If the BATT LOW LED remains on after replacing the battery in your Siemens Control Unit, verify that the correct type of battery is being used. The LOW BATT LED remains ON if an alkaline battery is used in PXC Compact models with extended temperature range operation.
  • G
    grantbookerSep 12, 2025
    What to do if the battery low warning is displayed on Siemens PXC Compact Control Unit?
    • N
      npatrickSep 12, 2025
      If the BATT LOW LED is on or the battery low warning is displayed at the operator's terminal of your Siemens Control Unit, check that the mylar insert was removed from the AA (LR6) battery holder. Check for correct polarity (+ to +) and (- to -). Check that the battery is properly seated in the battery holder. If needed, replace the battery.

Summary

Product Overview

PXC Compact Series Overview

General introduction to the PXC Compact Series controllers and their capabilities.

APOGEE Automation System Compatibility

Details on integration with APOGEE automation systems and field panels.

Protocol Compatibility

Information on BACnet/IP, Ethernet TCP/IP (P2), and RS-485 protocol support.

Supported Point Types

Configuration options for analog and digital I/O points for PXC models.

System Diagrams

Visual layout and terminal block connections for 16/24 and 36-point PXC Compact models.

Hardware Features and Specifications

General Hardware Features

Overview of PXC Compact hardware components, connectors, and features.

Power and Sensor Connections

Details on 24 Vdc external sensor power source and shield termination.

Memory and Backup Systems

Information on Flash ROM, RAM, and essential battery backup systems.

Backup Batteries (AA & Coin Cell)

Management, replacement, and troubleshooting of AA and coin cell backup batteries.

Processor, Memory, and Communication Specs

Technical specifications for processor, memory size, and communication interfaces.

Electrical and Environmental Specifications

Details on power requirements, I/O capabilities, and operating conditions.

Communication Ports and Connections

Information on HMI, Ethernet, RS-485, USB ports, and TX-I/O Island Bus.

FLN and P1 Mode Operation

Details on Field Level Network (FLN) support and P1 mode functionality.

HOA and Upgrade Kits

Features and installation of Hand-Off-Auto (HOA) switches and upgrade kits.

Advanced Features and Modules

PXC Compact on P1 Mode

Configuration and operation of PXC Compact controllers in P1 mode.

PXM10 S;T Operator Display Modules

Overview, features, and operation of PXM10S/T operator display modules.

Unitary Equipment Controller (UEC)

Introduction to the UEC controller and its FLN/ALN node operating modes.

Service and Troubleshooting

General Service Information

Guidelines for performing maintenance, troubleshooting, and corrective measures.

LED Status and Basic Troubleshooting

Interpreting RUN, BATT LOW, TX/RX LED indicators and initial checks.

Communication and Display Issues

Troubleshooting network communication failures and display problems.

TX-I;O Island Bus Troubleshooting

Diagnosing errors, module failures, and communication issues on the TX-I/O bus.

Module Replacement Procedures

Steps for replacing TX-I/O plug-in modules and complete module assemblies.

Siemens PXC Compact Series Specifications