PXC Compact Series
Technical Reference Manual
145-172
Building Technologies
2018
-09-25 Restricted

Table of Contents

Questions and Answers

  • S
    Sara FrancoAug 17, 2025
    How to troubleshoot Siemens Control Unit when analog input/output points are not reading as expected?
    • J
      Jacob JohnsonAug 17, 2025
      If the analog input/output points on your Siemens Control Unit aren't reading correctly, verify that all slope/intercept entries are correct. Also, ensure the sensor is functioning properly and replace it if necessary.
  • J
    Jacob AndersonAug 20, 2025
    What to do if the RUN LED is off on Siemens PXC-24 Compact Control Unit?
    • B
      blackdeborahAug 20, 2025
      If the RUN LED is off on your Siemens Control Unit, first verify that power is connected. Then, check the service box and transformer ON switches. If power is ON, verify that the application firmware has booted. Finally, measure voltage on 24V~ and (Terminals 1 and 2).
  • J
    Justin BrennanAug 23, 2025
    How to fix Siemens PXC-24 Compact when points cannot be read or commanded from the operator's terminal?
    • J
      Jacqueline HansenAug 23, 2025
      If points cannot be read or commanded from the operator's terminal on your Siemens Control Unit, verify that any failed points have been properly addressed. Also, verify the status of the points at the operator's terminal and ensure that points are not under Operator priority.
  • D
    Dawn MayAug 26, 2025
    What to do if the RUN LED is ON but no communication is possible with the HMI port on Siemens PXC-24 Compact?
    • G
      George ElliottAug 26, 2025
      If the RUN LED is ON but there's no communication with the HMI port on your Siemens Control Unit, verify that the HMI port and your terminal are set to the same communication speed. Also, ensure that the cable from the field panel to the operator's terminal is properly connected at both ends. Open the enclosure and verify that both ends of the HMI extension cable are properly connected. Try unplugging the extension cable and plugging directly into the HMI port.
  • C
    Christian GuerraAug 28, 2025
    Why is there no communication over the ALN trunk on Siemens Control Unit?
    • T
      Teresa KaneAug 28, 2025
      If there is no communication over the ALN trunk on your Siemens Control Unit, and the TX and RX LEDs are off or on solid, verify that the ALN trunk is securely connected to the ALN port on the Field Panel. On a two-wire ALN trunk, verify that the shield is connected to the enclosure ground and not the S-pin. Verify the field panel address and communication speed. Also, verify that the extended ALN trunk is operating.
  • A
    Allison JosephAug 31, 2025
    How to troubleshoot Siemens Control Unit when LAI point does not function properly?
    • B
      Brooke MosleyAug 31, 2025
      If an LAI point on your Siemens Control Unit isn't functioning correctly or shows as failed (*F*), verify that the field input device is within range. Also, make sure that points are properly terminated on the termination board or module. Confirm that the correct voltage is supplied to the device, as in a 4 to 20 mA device.
  • J
    James JohnsonSep 2, 2025
    How to troubleshoot Siemens Control Unit when LAO point does not function properly?
    • S
      Shannon BrownSep 3, 2025
      If an LAO point on your Siemens Control Unit is not functioning properly, displays as failed (*F*), and the output doesn't change when commanded, verify that the device connected to the point is functioning properly and is not shorted out. Also, verify that points are properly terminated on the termination board or module. Finally, verify that the correct voltage is supplied to the device.
  • T
    Tabitha LewisSep 5, 2025
    How do I fix no communication over the FLN trunk on Siemens PXC-24 Compact?
    • E
      Elizabeth SmithSep 5, 2025
      If there is no communication over the FLN trunk on your Siemens Control Unit, verify the FLN address and communication speed. Also, verify the FLN trunk is connected to the correct FLN port.
  • C
    cody06Sep 8, 2025
    Why does the BATT LOW LED remain on after battery replacement in Siemens PXC-24 Compact Control Unit?
    • D
      Debra HowardSep 8, 2025
      If the BATT LOW LED remains on after replacing the battery in your Siemens Control Unit, verify that the correct type of battery is being used. The LOW BATT LED remains ON if an alkaline battery is used in PXC Compact models with extended temperature range operation.
  • M
    michaeladamsSep 12, 2025
    What to do if the battery low warning is displayed on Siemens PXC-24 Compact?
    • L
      Lawrence WalshSep 12, 2025
      If the BATT LOW LED is on or the battery low warning is displayed at the operator's terminal of your Siemens Control Unit, check that the mylar insert was removed from the AA (LR6) battery holder. Check for correct polarity (+ to +) and (- to -). Check that the battery is properly seated in the battery holder. If needed, replace the battery.

Summary

Compact Series Product Overview

Firmware, Licensing, and Supported Point Types

Covers firmware revision, licensing, and an introduction to supported point types.

Supported Point Types

PXC Model Point Type Configurations

Lists configurable and dedicated point types for PXC-16, PXC-24, and PXC-36 models.

Hardware Features

Memory and Backup Batteries

Details memory types, Flash ROM, RAM, and backup batteries (AA, coin cell).

Communication Ports and Specifications

Covers communication connections, specs, and diagrams for HMI, Ethernet, RS-485.

PXC Compact on P1 Operation

Understanding PXC Compact on P1 and its Database

Explains what PXC Compact on P1 is and its three-part database structure.

P1 Mode Applications, Mapping, and Operation

Details P1 mode applications, point mapping, and operational aspects.

Smoke Control Application Requirements

Service Information and Troubleshooting

TX-I;O Island Bus and Module Troubleshooting

Troubleshoots TX-I/O Island Bus errors, module failures, and component replacement.

Siemens PXC-24 Compact Specifications

General IconGeneral
Number of I/O Points24
Power consumption15 VA / 8 W
Operating temperature-20 °C to +60 °C
Mounting TypeDIN rail
MountingDIN rail
Dimensions160 x 140 x 70 mm
Protection classIP20
Enclosure RatingIP20
Supply voltage24 V DC
Power Supply24 V DC
Communication ProtocolsBACnet MS/TP, Modbus RTU
CommunicationBACnet MS/TP, Modbus RTU
Communication InterfaceRS-485
Storage Temperature-40 °C to +70 °C
Relative Humidity10% to 95% (non-condensing)