Compact Series Product Overview 
16- and 24-Point Compact Series Diagram 
Technical Reference Manual 
 
16- and 24-Point Compact Series Diagram 
 
NOTE: 
The USB device port is now functional. It requires a computer device driver and 
standard computer terminal software, available on Standard Apps). 
 
PXC-16 and PXC-24 Features, Symbols, and Status LEDs. 
Terminal Block Connection 
1 
24V 
~ 
Supply voltage, 24 Vac input. 
2 
 
System neutral. 
3 
Functional earth. 
4 through 12 (PXC-16) 
4 through 18 (PXC-24) 
 
Digital Output relay, Normally Closed (NC), Common (C), 
Normally Open (NO). 
A (22 through 24) 
+ –   
RS-485 port. 
B 
10B/100B Ethernet port. 
C 
 
USB Device port. Supports a generic serial interface for an 
HMI or Tool connection. Does not support firmware flash 
upgrades. 
25, 27, 28 
 
Universal Input (+) (UI1 through UI3). 
26, 29 
– 
Signal Common. 
30, 31, 33, 34, 36 
 
Universal Input/Output (+) (U4 through U8).