Siemens Room Unit for Boiler Control CE1U2283en
Building Technologies Handling 2015-09-16
Operating
line
Operating
level
Function
Factory
setting
Range
Unit
ECO24 F 24-hour heating limit 0 -10…+10 °C
KORR F Room influence 4 0…20
BUILD F Time constant building 3 0...10
AMBON F Room influence ON/OFF
0 = OFF, 1 = ON
1 0-1
QSETB F Quick setback ON/OFF
0 = OFF, 1 = ON
1 0-1
SDR F Room temp limitation 0,5 0,5...4,0 °C
HC2SR
2)
F Room temperature setpoint for
heating circuit 2
20 5...35 °C
HC2SF
2)
F Flow temperature setpoint heating
circuit 2
80 20...80 °C
COOL 1)
COMFR E Comfort setpoint 22 5...30 °C
ECONM E Reduced setpoint 24 5...30 °C
DHW
COMFR F Nominal setpoint 55 35...70 °C
ECONM F Reduced setpoint 35 35...70 °C
SHOWR O Shower function setpoint 40 35...70 °C
HW MX F DHW setpoint max 65 35...70 °C
HW MN F DHW setpoint min 35 35...70 °C
L FCT F Legionella function
0 = OFF, 1 = ON
0 0...2
L TIME F Legionella function dwelling time 1 1...180 Min
L TEMP F Setpoint of legionella function 65 35...70 °C
CONF
HW PR F DHW program 1 0...2
COOL F COOLING ON/OFF
0 = OFF, 1 = ON
0 0-1
RESET O Reset to default parameters
0 = NO, 1 = YES
0 0-1
1) This menu is only visible if parameter COOL is ON
2) Only active when supported by BMU