4.2.2 Overview of settings
The table shows all available settings up to the heating engineer level. However,
certain operating lines may be hidden, depending on the type of unit.
E = End user, F = Heating engineer, O = OEM
TIME
hh:mm E Hours/minutes 00:00…23:59 hh:mm
DAY E Week day 1…7
TSPHC
MO…SU E Day selection MO 1…7
ON 1 E 1st phase on 06:00 00:00…23:59 hh:mm
OF 1 E 1st phase off 22:00 00:00…23:59 hh:mm
ON 2 E 2st phase on 24:00 00:00…23:59 hh:mm
OF 2 E 2st phase off 24:00 00:00…23:59 hh:mm
ON 3 E 3st phase on 24:00 00:00…23:59 hh:mm
OF 3 E 3st phase off 24:00 00:00…23:59 hh:mm
ON 4 E 4st phase on 24:00 00:00…23:59 hh:mm
OF 4 E 4st phase off 24:00 00:00…23:59 hh:mm
TSPCC 1)
MO…SU E Day selection MO 1…7
ON 1 E 1st phase on 10:00 00:00…23:59 hh:mm
OF 1 E 1st phase off 18:00 00:00…23:59 hh:mm
ON 2 E 2st phase on 24:00 00:00…23:59 hh:mm
OF 2 E 2st phase off 24:00 00:00…23:59 hh:mm
ON 3 E 3st phase on 24:00 00:00…23:59 hh:mm
OF 3 E 3st phase off 24:00 00:00…23:59 hh:mm
ON 4 E 4st phase on 24:00 00:00…23:59 hh:mm
OF 4 E 4st phase off 24:00 00:00…23:59 hh:mm
TSPHW
ON 1 E 1st phase on 06:00 00:00…23:59 hh:mm
OF 1 E 1st phase off 22:00 00:00…23:59 hh:mm
ON 2 E 2st phase on 24:00 00:00…23:59 hh:mm
OF 2 E 2st phase off 24:00 00:00…23:59 hh:mm
ON 3 E 3st phase on 24:00 00:00…23:59 hh:mm
OF 3 E 3st phase off 24:00 00:00…23:59 hh:mm
ON 4 E 4st phase on 24:00 00:00…23:59 hh:mm
OF 4 E 4st phase off 24:00 00:00…23:59 hh:mm
HEAT
COMFR E Comfort setpoint 20 5…35 °C
ECONM E Reduced setpoint 18 5…35 °C
NOFRS E Frost protection setpoint 5 5…35 °C
HC SL O Flow temp setpoint manual 80 20…80 °C
HC MX F Flow temp setpoint max OEM 80 20…80 °C
HC MN F Flow temp setpoint min 20 20…80 °C
SLOPE F Heating curve slope 1,5 0,1…4
SUWI F Summer/winter heating limit 18 8…30 °C