38 / 46
Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_05
Building Technologies ETS engineering 2018-09-14
Visible parameter name in ETS Range
(Default)
5.5.5 Room air quality sensor
CO
2
concentr.: Send following change by
5;10;20…500;750;1000
ppm
X X
CO
2
concentr.: Sensor correction (ppm)
CO
2
concentr.: Send cyclically after
CO
2
concentr.: Altitude above sea level (m)
5.5.6 Room air quality control
To display this section, enable the option “Activate room air quality control” in Device
Default switching point stage 1 (ppm)
Default switching point stage 2 (ppm)
Default switching point stage 3 (ppm) 400…2000 (1500) ppm
If the CO
2
concentration exceeds a switching point CO
2
, the control
value CO
2
for the related stage is switched on. The control value CO
2
is again switched off, if the CO
2
concentration returns to < switching
point CO
2
– hysteresis.
Control value stage 0 (%)
Control value stage 1 (%) (>stage 0)
Control value stage 2 (%) (>stage 1)
Control value stage 3 (%) (>stage 2)
If the CO
2
concentration exceeds a switching point CO
2
, the control
value CO
2
for the related stage is switched on. The control value
issues again the value of the next lower stage when CO
2
concentration < switching point CO
2
– hysteresis.
Send cyclically after
Do not send cyclically
1;2;3...30;45;60 (15 min)
min.
X X X X X X X
5.5.7 Device display parameters
Backlight Level 0; 10;…100 (60%) %
Active unit set °C; °F (°C)
Active audio feedback (buttons)
Display: Idle page
(HVAC operation and display)
Temperature
Relative humidity
X X X
Time to return to idle page (s) 3…120 (15 s) s