Siemens RDF410.21 - User Manual

Siemens RDF410.21
14 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
3
067
RDF310.2, RDF310.21 RDF410.21
Semi Flush-mount
Room Temperature
Controllers with LCD
RDF310…
RDF410…
for 2-pipe fan coil units
for use with compressors in DX type equipment
Output for on / off valve actuator or 1-stage compressor
3-speed fan control: Automatic or manual
Manual heating / cooling changeover or continuous Cooling only / Heating only
Operating modes: Normal operation, Standby
Adjustable commissioning and control parameters
Optional display of room temperature or setpoint
Minimum and maximum setpoint limitation
Operating voltage AC 230 V
Mounting on recessed rectangular conduit box, fixing centres 60.3mm
Additional features of RDF310.21
LCD backlight
Infrared remote control receiver
Additional features of RDF410.21
LCD backlight
Infrared remote control receiver
Auto Timer mode with 8 programmable timers
N3067en
01.10.2007
Building Technologies

Other manuals for Siemens RDF410.21

Question and Answer IconNeed help?

Do you have a question about the Siemens RDF410.21 and is the answer not in the manual?

Summary

Semi Flush-mount Room Temperature Controllers

Product Usage and Core Functions

Controller Functions Overview

Details core functions like temperature control, display, and fan speed management.

Operating Modes and Control Sequences

Available Operating Modes

Explains Normal operation, Standby, Auto Timer, and Energy Saving modes.

Advanced Features and Operation

Auto Timer Mode Functionality

Explains the Auto Timer mode with programmable timers for mode changes.

Configuration and Parameter Settings

Control Parameter Settings

Details how to adjust control parameters for optimization and lists parameter meanings.

Mechanical Design and Installation

Mounting and Installation Guidelines

Provides instructions for proper mounting location and wiring.

Technical Data and Standards

Technical Specifications Overview

Details electrical, operational, and environmental data for the controllers.

Overview

The Siemens RDF310... and RDF410... series are semi-flush-mount room temperature controllers with LCD displays, designed for 2-pipe fan coil units and compatible with compressors in DX type equipment. These controllers are suitable for managing room temperature in individual rooms and zones that are heated or cooled by 2-pipe fan coil units or cooled by a single compressor in DX type equipment.

Function Description

The controllers acquire room temperature via a built-in sensor and maintain the setpoint by delivering 2-position valve control commands or compressor output commands. They offer flexible control over a 3-speed fan (automatic or manual) and either a valve actuator in a 2-pipe system or a 1-stage compressor in DX type equipment.

Key operating modes include:

  • Normal Operation: The controller maintains the setpoint, which can be adjusted via the + and - buttons. The fan speed can be set to automatic or manual (low, medium, or high). The setpoint range can be limited to a minimum (P05) and maximum (P06) to prevent energy waste.
  • Standby Mode: Relevant heating or cooling setpoints are maintained, adjustable via parameters P03 and P04. Factory setting for both setpoints is OFF, meaning the controller is not active in Standby mode.
  • Auto Timer Mode (RDF410.21 only): The controller automatically switches between Normal operation and Energy Saving mode based on 8 preprogrammed timers. The display shows the Auto Timer mode symbol and the current operating mode (Normal operation or Energy Saving mode). The default fan speed in Auto Timer mode is automatic.
  • Energy Saving Mode: Setpoints for this mode can be adjusted via control parameters P01 and P02.

The controllers support manual heating/cooling changeover, or can be configured for continuous cooling only or heating only. An "always on" ventilation feature can be activated to prevent damage due to moisture in warm and humid climates by keeping the fan running at minimum speed 1 in the dead zone (P20).

Usage Features

The LCD display shows either the acquired room temperature or the setpoint of the current operating mode (selectable via P18). Heating and cooling symbols indicate the status of the fan coil, even in the neutral zone. Temperature and setpoint can be displayed in °F or °C (P17).

For the RDF410.21, an Auto Timer mode with 8 programmable timers allows for scheduled changes between Normal operation and Energy Saving mode. Each timer has a Normal operation start and end time, applicable to several weekdays. The 7-day time clock supports both 12-hour and 24-hour formats.

The RDF310.21 and RDF410.21 models include an infrared receiver, allowing remote control via the IRA210 infrared remote control (ordered separately). Remote functions include selecting operating mode (Standby, Normal operation, Auto Timer), adjusting the setpoint in Normal operation, and selecting fan mode (automatic or manual). A buzzer confirms receipt of remote commands. The infrared receiver can be disabled via parameter P25.

Maintenance Features

  • Parameter Settings: A number of control parameters can be readjusted to optimize control performance. These parameters can be set during operation without opening the unit and are maintained in the event of a power failure.
  • Parameter Reset: Factory settings for control parameters can be reloaded.
  • Sensor Calibration: If the displayed room temperature does not match the actual room temperature, the sensor can be recalibrated by changing parameter P07.
  • Power Failure Handling: In case of power failure, the internal clock stops but stores its last running time. This information is reloaded upon power-up, and the clock flashes until confirmed or readjusted.
  • Error Handling: If the room temperature is outside the measuring range (0-49 °C), the display shows the limiting temperature flashing. The controller will resume Normal operation once the temperature returns to the measuring range.

Important Technical Specifications

  • Operating Voltage: AC 230 V +10/-15%, 50/60 Hz.
  • Power Consumption: Max. 8 VA.
  • Outputs:
    • Fan control (Q1, Q2, Q3-N): AC 230 V, max. 4(2)A.
    • Control output (Y11-N, N.O.): AC 230 V, max. 4(2)A.
  • Inputs (Infrared receiver for RDF310.21 and RDF410.21):
    • Transmission distance: ≤ 7.5 m.
    • Orientation angle: ≤ ± 30°.
  • Switching Differential (adjustable): 0.5...4K.
    • Heating mode (factory setting): 2 K.
    • Cooling mode (factory setting): 1 K.
  • Setpoint Setting Range:
    • Normal operation: 5...40 °C.
    • Energy Saving mode (RDF410..): OFF, 5...40 °C.
    • Standby: OFF, 5...40 °C.
  • Built-in Room Temperature Sensor:
    • Measuring range: 0...49 °C.
    • Accuracy at 25 °C: < ± 0.5 K.
    • Temperature calibration range: ± 3.0 K.
  • Resolution of settings and display: 0.5 °C.
  • Environmental Conditions:
    • Operation: 0...+50 °C, <95% r.h.
    • Transport: -25...+60 °C, <95% r.h.
    • Storage: -25...+60 °C, <95% r.h.
  • Dimensions: 86mm x 86mm x 39mm (W x H x D). Mounting on recessed rectangular conduit box with fixing centers 60.3mm.
  • Weight: 0.17 kg.
  • Color: White, RAL 9003.
  • Conformity: CE (2004/108/EC, 2006/95/EC), C-Tick (AS/NSZ 4251.1:1994), RoHS (2002/95/EC).
  • Protection: IP 30 to EN 60 529.

Siemens RDF410.21 Specifications

General IconGeneral
TypeRoom Thermostat
Power SupplyAC 230 V
Frequency50/60 Hz
Degree of protectionIP30
Temperature settingRotary knob
Power Consumption2 VA
Relay Outputs1
MountingWall
Ambient temperature0 to 50 °C