Details core functions like temperature control, display, and fan speed management.
Explains Normal operation, Standby, Auto Timer, and Energy Saving modes.
Explains the Auto Timer mode with programmable timers for mode changes.
Details how to adjust control parameters for optimization and lists parameter meanings.
Provides instructions for proper mounting location and wiring.
Details electrical, operational, and environmental data for the controllers.
The Siemens RDF310... and RDF410... series are semi-flush-mount room temperature controllers with LCD displays, designed for 2-pipe fan coil units and compatible with compressors in DX type equipment. These controllers are suitable for managing room temperature in individual rooms and zones that are heated or cooled by 2-pipe fan coil units or cooled by a single compressor in DX type equipment.
The controllers acquire room temperature via a built-in sensor and maintain the setpoint by delivering 2-position valve control commands or compressor output commands. They offer flexible control over a 3-speed fan (automatic or manual) and either a valve actuator in a 2-pipe system or a 1-stage compressor in DX type equipment.
Key operating modes include:
The controllers support manual heating/cooling changeover, or can be configured for continuous cooling only or heating only. An "always on" ventilation feature can be activated to prevent damage due to moisture in warm and humid climates by keeping the fan running at minimum speed 1 in the dead zone (P20).
The LCD display shows either the acquired room temperature or the setpoint of the current operating mode (selectable via P18). Heating and cooling symbols indicate the status of the fan coil, even in the neutral zone. Temperature and setpoint can be displayed in °F or °C (P17).
For the RDF410.21, an Auto Timer mode with 8 programmable timers allows for scheduled changes between Normal operation and Energy Saving mode. Each timer has a Normal operation start and end time, applicable to several weekdays. The 7-day time clock supports both 12-hour and 24-hour formats.
The RDF310.21 and RDF410.21 models include an infrared receiver, allowing remote control via the IRA210 infrared remote control (ordered separately). Remote functions include selecting operating mode (Standby, Normal operation, Auto Timer), adjusting the setpoint in Normal operation, and selecting fan mode (automatic or manual). A buzzer confirms receipt of remote commands. The infrared receiver can be disabled via parameter P25.
| Type | Room Thermostat |
|---|---|
| Power Supply | AC 230 V |
| Frequency | 50/60 Hz |
| Degree of protection | IP30 |
| Temperature setting | Rotary knob |
| Power Consumption | 2 VA |
| Relay Outputs | 1 |
| Mounting | Wall |
| Ambient temperature | 0 to 50 °C |