11/14
Siemens RDF300…/RDF340 / RDF400… / RDF600... Flush-mounted Room thermostats CE1N3076en
Building Technologies 2018-12-27
Function input:
External temperature sensor, heating/cooling
changeover sensor, operating mode switchover
contact, dewpoint monitor contact, enable electrical
heater contact, alarm contact
Selectable
X1: P38
X2: P40
Switching differential, adjustable
Heating mode (P30)
Cooling mode (P31)
2 K (0.5...6K)
1 K (0.5...6K)
Setpoint setting and range
Comfort (P08)
Economy (P11-P12)
Protection (P65-P66)
21°C (5...40 °C)
15°C/30°C (OFF, 5...40 °C)
8°C/OFF (OFF, 5...40 °C)
Multifunctional input X1/X2
Input X1
Input X2
Selectable 0…6
3: (P38) operating mode
switchover
2: (P40) heating/cooling
changeover sensor
Built-in room temperature sensor
Measuring range
Accuracy at 25 °C
Temperature calibration range
0…49 °C
< ± 0.5 K
± 3.0 K
Settings and display resolution
Setpoints
Current temperature value displayed
0.5 °C
0.5 °C
Storage
Climatic conditions
As per IEC 60721-3-1
Class 1K3
Transport
Climatic conditions
As per IEC 60721-3-2
Class 2K3
Operation
Climatic conditions
As per IEC 60721-3-3
Class 3K5
1)
EU Conformity (CE)
CE1T3076_1
CE1T3076xx_2en_C1
*)
CE1T3076xx_3en_C1
*)
Degree of protection of housing IP 30 to EN 60529
Protective class II as per EN 60730-1
Pollution class Normal
The product environmental declarations CE1E3076_1, CE1E3076_2, CE1E3076_3
*)
contain data on environmentally compatible product design and assessments (RoHS
compliance, materials composition, packaging, environmental benefit, disposal).
Connection terminals Solid wires or prepared
stranded wires
1 x 0.4…1.5 mm
2
Housing front color RAL 9003 white
Weight RDF3..., RDF4...
RDF600...
0.220 kg
0.150 kg
*) The documents can be downloaded from http://siemens.com/bt/download.
1) No condensation is allowed.
Operational data
Environmental
conditions
Standards and
directives
Environmental
compatibility
General