Certification
6.1.11Other Approvals
6.1.11 Other Approvals
This device meets the requirements of the following additional standards:
• IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
• EN50121-4
Railway applications – Electromagnetic Compatibility – Emission and Immunity
of the Signaling and Telecommunications Apparatus
• EN50121-3-2
Railway applications – Electromagnetic Compatibility – Rolling Stock Apparatus
• EN 50155
Railway applications – Rolling stock – Electronic equipment
6.2 EMC and Environmental Type Tests
The RUGGEDCOM RSG907R has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Tests
Test Description Test Levels Severity
Levels
Enclosure
Contact
± 8 kV 4IEC
61000-4-2
ESD
Enclosure Air ± 15 kV 4
IEC
61000-4-3
Radiated RFI Enclosure
Ports
20 V/m
Signal Ports ± 4 kV @ 2.5 kHz, 5 kHz 4
DC Power
Ports
± 4 kV @ 2.5 kHz, 5 kHz 4
AC Power
Ports
± 4 kV @ 2.5 kHz, 5 kHz 4
IEC
61000-4-4
Burst (Fast Transient)
Earth
Ground Ports
± 4 kV @ 2.5 kHz, 5 kHz 4
Signal Ports ± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4
DC Power
Ports
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
3
IEC
61000-4-5
Surge
AC Power
Ports
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4
IEC
61000-4-6
Induced (Conducted) RFI Signal Ports 10 V 3
40
RUGGEDCOM RSG907R
Installation Manual, 10/2020, C79000-G8976-1387-10