Certification
6.2EMC and Environmental Type Tests
Test Description Test Levels Severity
Levels
DC Power
Ports
10 V 3
AC Power
Ports
10 V 3
Earth
Ground Ports
10 V 3
IEC
61000-4-8
Magnetic Field Enclosure
Ports
100 A/m Continuous
1000 A/m for 1 s
IEC
61000-4-9
Pulse Magnetic Field Enclosure
Ports
300 A/m 4
IEC
61000-4-11
Voltage Dips and Interrupts AC Power
Ports
30% for 0.5 Cycles
60% for 5 Cycles
100% for 250 Cycles
Signal Ports 30 V Continuous
300 V for 1 s
4IEC
61000-4-16
Mains Frequency Voltage
DC Power
Ports
30 V Continuous
300 V for 1 s
4
IEC
61000-4-17
Ripple on DC Power Supply DC Power
Ports
15% 4
IEC
61000-4-18
Damped Oscillatory Wave Slow
Damped
2.5 kV Common
100 kHz or 1 MHz
3
IEC
61000-4-29
Voltage Dips and Interrupts DC Power
Ports
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
Signal Ports 2 kV (Failsafe Relay Output)
DC Power
Ports
2 kV or 2.8kV DC
Dielectric Strength
AC Power
Ports
2 kV
Signal Ports 5 kV (Failsafe Relay Output)
DC Power
Ports
5 kV
IEC
60255-27
HV Impulse
AC Power
Ports
5 kV
EMC Immunity Type Tests per IEEE 1613
Note
The RUGGEDCOM RSG907R meets Class 2 requirements for an all-fiber
configuration and Class 1 requirements for copper ports. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
RUGGEDCOM RSG907R
Installation Manual, 10/2020, C79000-G8976-1387-10
41