Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
2.45 LPB segment address
The segment address and the device address are used as destinations in the bus
system. To ensure communication, each device must be correctly addressed.
Setting range Unit Factory setting
0...14 Increment 0
Entry of the segment address is especially important when used in a system. With this
setting, the system can be subdivided into a number of segments.
0 Heat generation segment
1...14 Heat consumer segment
A bus segment is comprised of a number of devices that are used in the same place of
application. All devices in a segment must carry the same segment address.
Addressing is part of engineering. For detailed information, refer to LPB System
Engineering, Basic Documentation (reference number CE1P2370E).
Description