3.10 Control of boiler pump
Boiler pump control mode can be selected.
The setting defines the criteria according to which the boiler pump shall be operated.
Setting range Unit Factory setting
0/1 - 0
The settings have the following meaning:
0 The boiler pump operates when there is a demand for heat.
In that case, the boiler pump responds to locking signals.
1 The boiler pump operates when there is a demand for heat or when the burner
operates. In that case, the boiler pump does not respond to locking signals
(protective boiler start-up).
Benefit
Description
Setting
Effect