30.3.2 Overriding the operating mode
From the QAW70, the controller’s operating mode can be overridden. This is made with
the operating mode button and the economy button.
To enable the room unit to act on the controller, the latter must be in automatic mode.
The actions of the QAW's operating mode button on the controller are as follows:
Operating mode QAW70 Operating mode RVD230
Automatic operation; temporary overriding with the
economy button of the QAW70 possible
Economy button off (lit): Nominal room temperature
Economy button on (not lit): Reduced room temperature
Standby
If the room unit overrides the controller’s operating mode, the operating mode button
on the controller flashes.
30.3.3 Knob for readjusting the room temperature
Using the knob of the QAW70, the nominal room temperature setpoint can be read-
justed by a maximum of ±3 °C.
The adjustment of the room temperature setpoint on the RVD230 will not be affected by
the QAW70.
30.3.4 Effects of the individual QAW70 operating lines on the
RVD230
Op. line
QAW70
Function, parameter Effect on the RVD230, notes
1 Nominal room temperature
setpoint
Overrides the setting on the controller
2 Reduced room tempera-
ture setpoint
Overrides the setting on the controller
3 D.h.w. temperature set-
point
Overrides the normal setpoint adjustment on
the controller. The setting range (controller
operating line 117) remains valid
4 Weekday For entering the heating program
5 Start of heating period 1 Changes the time switch settings in the con-
troller
6 End of heating period 1 Changes the time switch settings in the con-
troller
7 Start of heating period 2 Changes the time switch settings in the con-
troller
8 End of heating period 2 Changes the time switch settings in the con-
troller
9 Start of heating period 3 Changes the time switch settings in the con-
troller
10 End of heating period 3 Changes the time switch settings in the con-
troller
11 Entry of weekdays 1…7 Changes the time switch settings in the con-
troller
12 Entry of time of day Changes the time of day in the controller