Siemens Building Technologies Basic Documentation RVD230 CE1P2383en
HVAC Products 7 Function block End-user d.h.w. 27.05.2004
7 Function block End-user d.h.w.
7.1 Operating lines
Line Function, parameter Unit Factory setting Range
17 Weekday for entering the d.h.w. program Current weekday 1…7, 1-7
18 Start of release period 1 hh:min 06:00 --:-- / 00:00…24:00
19 End of release period 1 hh:min 22:00 --:-- / 00:00…24:00
20 Start of release period 2 hh:min --:-- --:-- / 00:00…24:00
21 End of release period 2 hh:min --:-- --:-- / 00:00…24:00
22 Start of release period 3 hh:min --:-- --:-- / 00:00…24:00
23 End of release period 3 hh:min --:-- --:-- / 00:00…24:00
41 Setpoint d.h.w. temperature Normal °C 55 variable
42 Setpoint d.h.w. temperature Reduced °C 40 8… Normal setpoint
7.2 D.h.w. heating program
The d.h.w. heating program of the RVD230 provides a maximum of 3 release periods
per day; also, every weekday can have different release periods. Every release period
is defined by a start and an end time.
Using "1-7" on operating line 17, it is possible to enter a d.h.w. heating program that
applies to all weekdays. This simplifies the settings: If the weekend times are different,
first enter the times for the entire week, then change days 6 and 7 as required.
The settings are sorted and overlapping release periods combined.
By setting --:-- at the start or at the end, the release period will be cancelled.
However, d.h.w. heating can also be released according to other programs. The selec-
tion is to be made on operating line 101.
7.3 Adjustment of setpoints
The nominal d.h.w. temperature setpoint is to be adjusted on operating line 41. Its
setting range depends on the type of plant (for details, refer to section 19.5)
The reduced d.h.w. temperature setpoint can be adjusted on operating line 42 between
8 °C and the nominal setpoint. It is used with the d.h.w. program between the release
periods (refer to above section 7.2)
Nom
Red
w
BW
2381D06
t
06:00 08:00 11:30 13:30 16:00
Nom Nominal setpoint
Red Reduced setpoint
t Time
w
BW
D.h.w.setpoint