33/130
Siemens Building Technologies Basic Documentation RVD230 CE1P2383en
HVAC Products 8 Function block Display of actual sensor values 27.05.2004
8 Function block Display of actual sen-
sor values
8.1 Operating lines
Line Function, parameter Unit Factory setting Range
24 Room temperature (terminal A6) °C Display function
25 Outside temperature °C Display function
26 D.h.w. temperature °C Display function
27 Flow temperature heating circuit °C Display function
8.2 Displays
• Room temperature:
If a room temperature sensor or room unit is connected to the PPS interface (A6), the
temperature acquired will be displayed
• Outside temperature:
The displayed temperature is delivered by the analog outside sensor (connected to B9)
or via data bus (refer to subsection 21.2.4 "Outside temperature source").
If buttons
and are pressed for 3 seconds, the displayed outside temperature will
be adopted as the composite and the attenuated outside temperature (outside tem-
perature reset)
• D.h.w. temperature:
The temperature displayed is that acquired with the d.h.w. sensor. Depending on the
plant configuration, this can be d.h.w. flow sensor B3 (plant types x–4) or storage tank
sensor B31 (other plant types with the exception of x–0).
If button
or is pressed, the controller will display the current setpoint
• Flow temperature heating circuit:
The temperature displayed is that measured with sensor B1.
Exceptions:
− Plant types 3–x and 7–2:
The temperature displayed is that measured with sensor B12
− Plant types 0–x:
No display
If button
or is pressed, the controller will display the current setpoint