Siemens Building Technologies Basic Documentation RVD230 CE1P2383en
HVAC Products 27 Function block DRT and maximum limitation of the return temperature 27.05.2004
27.5 Integral action time of the limitation func-
tions
With the maximum limitations of the return temperature, the integral action time deter-
mines the rate at which the flow temperature setpoint will be reduced.
Short integral action times lead to faster reductions
Long integral action times lead to slower reductions
With this setting (on operating line 178), the impact of the limitation function can be
matched to the type of plant.