57/126
Siemens Building Technologies Basic documentation RVD240 CE1P2384en
HVAC Products 14 Function block Valve actuator heating circuit 27.05.2004
14.5 Minimum limitation of the flow temperature
The minimum limit value is to be set on operating line 96. The setting range for the
minimum limit value lies between 8 °C and the maximum limit value (setting on operat-
ing line 95).
At the limit value, the heating curve runs horizontally. This means that the flow tem-
perature setpoint cannot fall below the minimum value.
This function can be deactivated (entry of --- on operating line 96).