EasyManua.ls Logo

Siemens RVD240 - Page 71

Siemens RVD240
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
71/126
Siemens Building Technologies Basic documentation RVD240 CE1P2384en
HVAC Products 17 Function block Extra legionella functions 27.05.2004
If a maximum d.h.w. charging time has been set, it also acts here. If the legionella set-
point is not reached, the legionella function will be interrupted and resumed on comple-
tion of the maximum charging time.
The legionella setpoint will not be affected by the maximum of the d.h.w. temperature
setpoint.

Table of Contents

Related product manuals