HVAC Products CC1B7865en 05.12.2002 37/57
7. Parameter settings
The parameter is shown on the lower / setpoint display (green) and the parameter value
on the upper / actual value display (red).
Parameter
Display
Value range Factory
setting
Remarks
Actuator running
time
tt
10...3000 s 15 s Running time of the valve for use with
floating controllers
Switch-on threshold
for burner stage II
1)
HYS1
0...-199.9 digit -5 ð Section 5.5.1 «Heating curve slope»
Switch-off threshold
stage II
1)
HYS2
0...HYS3 digit 3 ð Section 5.2 «High-fire operation»
Upper switch-off
threshold
1)
HYS3
0...999.9 digit 5 ð Section 5.2 «High-fire operation»
Response threshold
q
0...999.9 0 ð Section 5.6 «Response threshold
Heating curve slope
H
0...4 1 ð Section 5.5.1 «Heating curve slope»
Parallel
displacement
1)
P
-90...+90 0 ð Section 5.5 «Weather-dependent
setpoint shif
1)
Setting of the decimal place has an impact on this parameter.
10
AL
7865p06/0200