44/57 CC1B7865en 05.12.2002 HVAC Products
8. Configuration
G
The setting of the decimal place has an impact
on the parameters that are dependent on the
actual value!
0000
C113
7865p05/0200
Unit address
Address 0 0 0
Address 1 01
... ...
Address 99 99
Decimal place, unit, Baud rate
No decimal place, degrees Celsius, 9600 Bd 0
One decimal place, degrees Celsius, 9600 Bd 1
No decimal place, degrees Fahrenheit, 9600 Bd 2
One decimal place, degrees Fahrenheit, 9600 Bd 3
No decimal place, degrees Celsius, 19200 Bd ¹) 4
One decimal place, degrees Celsius, 19200 Bd ¹) 5
No decimal place, degrees Fahrenheit, 19200 Bd ¹) 6
One decimal place, degrees Fahrenheit, 19200 Bd ¹) 7
No decimal place, degrees Celsius, 4800 Bd ¹) 8
One decimal place, degrees Celsius, 4800 Bd ¹) 9
No decimal place, degrees Fahrenheit, 4800 Bd ¹) A
One decimal place, degrees Fahrenheit, 4800 Bd ¹) b
Signal for out-of-range
Limit comparators OFF 0
Limit comparators ON 1
Factory setting 0 1 1 0
¹) Only with RWF40.0X2B97
8.3 C113 instrument address, dimensional unit, out-of-range