Building Technologies Division User Manual RWF55... CC1U7867en
Infrastructure & Cities Sector 5 Operating modes 05.11.2013
Cold start of plant also works when the RWF55 is used as a cooling controller.
In that case, the limit value is calculated as follows:
Limit value = 2 x (HYS4-HYS6)
Operating mode: Modulating 3-position output
HYS4 = 5 K
HYS6 = -5 K
w = -30 °C
Limit value = 2 x (5 + 5) = 2 x (10) = +20 K
When the actual value lies above -10 °C, cooling is immediately started in high-fire
mode in place of low-fire mode.
Cooling controller
Example