Technical data
Siemens AG Dk-Nr. 283641 Edition 05.95 5
SIMADYN D Hardware User Manual
5. Technical data
INSULATION VOLTAGE acc. to VDE 0160/Draft, came into force 12/90
Electrical isolation:
- between inputs and outputs
- between input circuits
AMBIENT TEMPERATURE 0 to 55
o
C
STORAGE TEMPERATURE -40 to 70
o
C
HUMIDITY CLASS acc. to DIN 40040 F
DEGREE OF PROTECTION acc. to DIN 40050IP00
MECHANICAL STRESSING acc. to SN 29010 Class 12
MOUNTING SYSTEM Can be snapped onto mounting rails
DIMENSIONS 118mm*135mm*42mm
WEIGHT approx. 320g
Supply voltage (V
v
)
(DC voltage)
SIMADYN D side System side at
24V
System side at
48V
-Nominal value
-Permissible range
-Briefly
24V
20V to 30V
1.5*V
rated
Duration 0.5s
24V
20V to 30V
1.5*V
rated
Duration 0.5s
48V
40V to 60V
1.5*V
rated
Duration 0.5s
Current drain (nominal value) 90mA 50mA 50mA
8 inputs:
-Input voltage
for "1" signal
for "0" signal
-Input current (1 signal)
+13V to +30V
-3V to +6V
or input open-circuit
6mA
+26V to +60V
-3V to +12V
or input open-circuit
6mA
8 outputs:
-Output voltage
for "1" signal
for "0" signal
-Output current
for "1" signal
-Residual output current
for "0" signal
-Continuous short-circuit current
(U
v
- 3)V
0 to +3V
max. 10mA
max. 4uA
max. 17mA

Related product manuals