3.2 Line protection applications of 3VA molded case circuit breakers
3VA molded case circuit breakers with IEC certificate
124 Manual, 03/2019, A5E03603177010-03
Advantages of 3VA2 molded case circuit breaker with ETU340 ELISA over fuses
The extensive internal and external accessories of the 3VA2 molded case circuit breaker
can be used.
When the EFB300 external function box is used, it is possible to output alarms from the
ETU, e.g. reason for tripping overload warning (overload or short circuit).
Adjustable operating current for the overload release, thereby making it possible to use
smaller cable cross sections
Selectivity to downstream fuses 1 : 1.6
Can be closed again immediately after tripping and troubleshooting; no need to stock
replacement fuses
Note
The minimum short-circuit current at the line side I
‘‘
kmin
must be at least 7 times the circuit
breaker's rated current I
n
to trip the molded case circuit breaker after 5 s in compliance with
IEC 60364-4-43, DIN VDE 0100-430.
ETU340 ELISA 3-pole:
ETU340 ELISA 4-pole:
Line protection function ELISA LI
The ETU340 ELISA electronic trip unit has:
Simulation of the tripping characteristic of a fuse in a circuit breaker
Adjustable parameter setting I
r
for overload protection (L)
Increased, fixed parameter setting I
i
for instantaneous short-circuit protection (I)
I
i
= 15 x I
r
With 4-pole versions only: Neutral conductor protection (N) which can be deactivated
Permanently active thermal memory, cannot be deactivated