4.9 Communication and system integration
3VA molded case circuit breakers with IEC certificate
488 Manual, 03/2019, A5E03603177010-03
4.9.3.2
Features
Working in conjunction with the connected 3VA molded case circuit breakers with ETUs 5-
series and 8-series, the COM800/COM100 breaker data server supplies the following
information about the power distribution system:
Condition of the 3VA molded case circuit breaker
Tripping history with time stamp, cause of trip and number of trip events for breakers with
ETUs 5-series and 8-series
Minimum and maximum values of measured variables
Limit-value monitoring for measured variables in the 3VA molded case circuit breakers
Load curves with power demands, e.g. 15-minute demands
Energy values such as active energy (kWh) and reactive energy (kvarh)
Power supply to connected 3VA molded case circuit breakers
Three simultaneous communication connections via the integrated Ethernet interface
(e.g. DSP800, powermanager and, temporarily, powerconfig)
4.9.4
Communication with ETUs
Electronic trip units allow detailed setting of protection parameters from a central location.
They record measured variables and maintenance information in order to support power and
installation monitoring.
The electronic trip units (ETUs) provide the following protection functions:
Overload protection L ("L" = Long time)
Short-time delayed short-circuit release S ("S" = Short time) for time-selective response in
case of a short-circuit
Instantaneous short-circuit release I ("I" = Instantaneous)
Protection of the neutral conductor against overload and short-circuit ("N" = neutral)
Protection against residual currents to ground G ("G" = Ground fault)
4.9.4.1
Area of application
Communication-capable ETUs are deployed for any application which requires the following
functions:
Diverse protection functions
Finer setting options for protection functions
Metering functions
For 50 and 60 Hz networks (45 to 65 Hz)
The communication option provides a wide range of information about the status of the
molded case circuit breaker, as well as the actual measured values.