4.8 Residual current devices
3VA molded case circuit breakers with IEC certificate
Manual, 03/2019, A5E03603177010-03
471
Connection of residual current device for 2-phase operation
The following 3 and 4-pole molded case circuit breakers equipped with a residual current
device can be operated in two phases (L to L) with 2-pole switching:
Loadside residual current devices for 3VA1: RCD320 and RCD520
Permissible rated operational voltage: 127 480 VAC 50/60 Hz
Side mounted residual current devices for 3VA1: RCD310 and RCD510
Permissible rated operational voltage: 127 480 VAC 50/60 Hz
Loadside residual current devices for 3VA2: RCD820
Permissible rated operational voltage: 127 690 VAC 50/60 Hz
Wiring example for 2-phase operation, 2-pole switching (3 and 4-pole molded case circuit
breakers)