3VA molded case circuit breakers with IEC certificate
Manual, 03/2019, A5E03603177010-03
663
Rated residual current
The rated residual current
I
Δn
is the fault (residual) current for which residual current-
operated circuit breakers are designed. The residual current rating is declared on the rating
plate of the device.
Rated service short-circuit breaking capacity
The rated service short-circuit breaking capacity
I
cs
is the short-circuit current determined by
the operational voltage that a molded case circuit breaker is capable of interrupting
repeatedly (test sequence 0 - C0 - CO, formerly P - 2). After a molded case circuit breaker
has interrupted a short circuit, it can continue to carry the rated operational current despite
increased self-heating and will trip again in the event of a short circuit.
Rated short-circuit breaking capacity
The rated short-circuit breaking capacity
I
cn
of a molded case circuit breaker is the maximum
current that the circuit breaker can safely interrupt at a specific rated operational voltage and
rated frequency. It is specified as an rms value.
With AC molded case circuit breakers, the rated short-circuit breaking capacity must be
independent of the magnitude of the DC component. The rated short-circuit breaking
capacity also ensures that the molded case circuit breaker can interrupt every current up to
the rated short-circuit breaking capacity in the event of a line-frequency recovery voltage with
110% of the rated operational voltage.
This applies:
To alternating current at every value of the power factor, but not lower than the value
defined in the relevant test specification.
To direct current (unless otherwise specified by the manufacturer) with every time
constant, but not greater than the value defined in the relevant test specification.
The short-circuit breaking capacity does not apply in the event of a recovery voltage at line
frequency above 110% of the rated operational voltage.
Rated short-circuit making capacity
The rated short-circuit making capacity
I
cm
of a molded case circuit breaker is the maximum
current that the circuit breaker can safely interrupt at a specific rated operational voltage and
rated frequency. Unlike other characteristic data, this is specified as a peak value.
With AC molded case circuit breakers, the rated short-circuit making capacity must be at
least equal to the rated short-circuit breaking capacity multiplied by a factor n.
The rated short-circuit making capacity is calculated to allow the molded case circuit breaker
to conduct the current during closing at a voltage of up to 110% inclusive of the rated
operational voltage.