Operation and Display
4.3 Key Definition
SICAM P35 P36, 3-phase Multi-Function Power Meter, User Manual
E50417-H8940-C562-4, Release Date 06.2018
26
Key Setting Parameters
1. Key functions at parameter setting mode
Example 15:
This screen shows reactive pulse constant items.
At cyclic display mode, press "▲" or "▼" to enter key display
mode, press " " to switch to area B, and press "▲" or "▼"
to switch to reactive pulse constant items.
In the figure, reactive constant=5,000 imp/kWh.
Example 16:
This screen shows Device ID display items.
At cyclic display mode, press "▲" or "▼" to enter key display
mode, press " " to switch to area B, and press "▲" or "▼"
to switch to Device ID display items. Device
ID=000000000001.
Example 17:
This screen shows error code display items.
At cyclic display mode, press "▲" or "▼" to enter key display
mode, press " " to switch to area B. Press "▲" or "▼" again
to switch to fault code display items. "E" means fault prompt,
the 7 bits from right to left mean respectively phase A loss,
phase B loss, phase C loss, voltage phase inversion, phase C
reverse, phase B reverse, and phase A reverse. For example,
"E0110001" means phase B and phase C loss and phase C
reverse fault occurs.
Key symbol ▲▼
Function
a) "▲" to switch digit or flip over;
b) "▼" to move cursor or flip over.
a) Press " " and " " at the same time to enter
setting screen.
b) Press " " to enter next menu or "confirm" parameter
setting.
c) Press " " to return to previous menu or "cancel" pa-
rameter setting
1
.
1.Press " " once after adjusting parameters with "▲" and "▼" to display "Sure", and press " " once
again to alter parameters. Pressing " " immediately after "Sure" appears will cancel current alteration.