04.05 7 - Maintenance
Siemens AG 7VV3003-8TA74 ENGLISH 27
SICROWBAR 7VV3003 DC-Surge Suppressor Operating Instructions
The times specified below can be used as a guide for replacing a device or components and apply under the
following conditions:
The replacement device(s) or part(s) are available on site
Specialist personnel are available on site
Ambient conditions are appropriate for carrying out the required work
To be replaced MTTR Prerequisite
SICROWBAR device 50 min
PCB ignition module C98043-A7061-L* 15 min Device remains installed
PCB voltage sensing module 449404.9210.50 30 min Device remains installed
PCB high-speed de-excitation option C98043-A7060-L1 15 min Device remains installed
PCB = Printed Circuit Board
MTTR = Mean Time To Restoration
1) Unplug cable connections
2) Unscrew 2x M4 screw and 2x
hexagonal spacer
3) Replace board
Fig. 10 Replace ignition module