Parameters/address space
4.1 Parameters
Digital input module DI 8x24VDC ST (6ES7131-6BF01-0BA0)
Manual, 02/2019, A5E03574157-AF
17
Parameters
Value range
Default
Configu-
ration in
RUN
Scope with configuration soft-
ware, e.g. STEP 7 (TIA Portal)
GSD file
PROFINET IO
GSD file
PROFIBUS DP
Input delay
none
0.05 ms
0.1 ms
0.4 ms
0.8 ms
1.6 ms
3.2 ms
12.8 ms
20 ms
3.2 ms yes Channel Module
1
Potential group
Use potential group of the
left module (module
plugged into a dark-
colored BaseUnit)
Enable new potential
group (module plugged in-
to light-colored BaseUnit)
Use potential
group of the left
module
no Module Module
2
Due to the limited number of parameters of a maximum of 244 bytes per ET 200SP station with a PROFIBUS GSD
configuration, the parameter assignment options are restricted. The parameter length of the I/O module is 3 bytes with
PROFIBUS GSD configuration. If necessary, you can set this parameter by using the data record 128, see the appendix
"Parameter data record".