Parameters/address space
4.1 Parameters
Digital input module DI 8x24VDC ST (6ES7131-6BF01-0BA0)
Manual, 02/2019, A5E03574157-AF
17
Scope with configuration soft-
ware, e.g. STEP 7 (TIA Portal)
Input delay
• none
• 0.05 ms
• 0.1 ms
• 0.4 ms
• 0.8 ms
• 1.6 ms
• 3.2 ms
• 12.8 ms
• 20 ms
3.2 ms yes Channel Module
1
Potential group
• Use potential group of the
left module (module
plugged into a dark-
colored BaseUnit)
• Enable new potential
group (module plugged in-
to light-colored BaseUnit)
Use potential
group of the left
module
no Module Module
Due to the limited number of parameters of a maximum of 244 bytes per ET 200SP station with a PROFIBUS GSD
configuration, the parameter assignment options are restricted. The parameter length of the I/O module is 3 bytes with
PROFIBUS GSD configuration. If necessary, you can set this parameter by using the data record 128, see the appendix