Parameter data record
A.1 Parameter assignment and structure of the parameter data record
Digital input module DI 8x24VDC ST (6ES7131-6BF01-0BA0)
30 Manual, 02/2019, A5E03574157-AF
Error transferring the data record
The module always checks all the values of the transferred data record. Only if all the values
were transferred without errors does the module apply the values from the data record.
The WRREC instruction for writing data records returns corresponding error codes when
errors occur in the STATUS parameter, see also the description of the "STATUS" parameter
in the STEP 7 online help).
The following table shows the module-specific error codes and their meaning for the
parameter data record 128.
Error code in STATUS parameter
(hexadecimal)
Solution
Byte 0
Byte 1
Byte 2
Byte 3
DF 80 B0 xx Number of the data record un-
known.
Enter a valid number for the data record.
DF
80
B1
xx
Enter a valid value for the data record length.
DF 80 B2 xx Slot invalid or cannot be accessed.
Check the station whether the module is
plugged or drawn.
Check the assigned values for the pa-
rameters of the WRREC instruction.
DF 80 E0 xx Wrong version or error in the
Correct the version, length and number of
parameter blocks.
DF
80
E1
07
Check the parameters of the module.