Explanation
A I 4.0
FP M 101.0
= M 104.0
m2: CALL SFB53, DB53
REQ :=M104.0 Write request
ID :=DW#16#200
INDEX :=80
Module address
Data record number 80
LEN :=11 Length 11 bytes
DONE :=M51.7
BUSY :=M51.0
ERROR :=M51.6
STATUS :=MD92
RECORD :=P#DB80.DBX0.0 BYTE 11
A M 51.0
SPB m2
BE
Block status or error information
Source area in DB80
DB80: Transparent message format
Byte Initial value (hex) Comment (Hex)
0 00 Req_Control
(00 = Transparent message format.
40 = Transparent message format with SHC sequence)
1 05 Number of preamble bytes (05-14)
2 82 Start character
(02 = Short Frame with command 0)
(82 = Long Frame with other commands)
3 98 Address
(with command 0, the address is exactly 1 byte long and has
the value 0.)
4 CF
5 38
6 84
7 F0
8 01 Command (CMD)
9 00 Length in bytes
10 98 Checksum (CHK)
(calculated as EXOR addition starting from byte 2 "Start
character" up to the last byte of the command. The check‐
sum does not have to be sent with the request.)
A HART command can also be sent in compact message format. In this case, the data transmitted
via DB 80 is reduced to 4 bytes.
HART operating data records
A.3 HART request and response data records