5.3 Module/channel parameters
De󹪝nition
Module/channel parameters are speci󹪝c parameters whose con󹪝guration can a󹪜ect the entire
module or channels.
Description
The parameters of the I/O module are displayed in the "Properties" dialog of the module in HW
Con󹪝g on the following tabs:
"Parameters" tab
"Redundancy" tab
This tab is displayed for redundant I/O modules.
The following module/channel parameters are available.
"Parameters" tab
Parameter Value range Default Re-parame‐
terization in
RUN
E󹪟ciency range
F-parameters
F_source_address
(Page 27)
1 (display only)
a
1 No Module
F_destination_address
(Page 27)
1 to 65534 Preset automatically
b
No Module
F_monitoring time (ms)
(Page 28)
10 ms to 65535 ms 2500 No Module
Cross-channel
Cross-channel parameters act on all identically named parameters of the channels of the module and thus allow a higher-level
setting.
Measurement type
(Page 31)
deactivated
2‑wire
4‑wire
2‑wire No Channel
Measuring range
(Page 31)
0..20mA
4..20mA
4..20mA No Channel
Smoothing (Page 29)
1 (none)
4
16
64
1 No Channel
Diagnostics wire break
(Page 32)
deactivated
activated
activated No Channel
Parameters/address space
5.3 Module/channel parameters
F-AI 8xI 2-/4-wire HART HA
Equipment Manual, 09/2021, A5E50557845-AA 23