Parameter Channel / sensor supply
HART enabled In the measuring range 4 to 20 mA: Activated / deactivated
Number HART message frame repeti‐
tions
In the measuring range 4 to 20 mA: 0 to 10
Diagnostics HART In the measuring range 4 to 20 mA: Activated / deactivated
Con󹪝guration in the safety program
For safety-oriented applications according to SIL3/Cat.4/PLe, perform a discrepancy analysis
with 1oo2 evaluation (in S7 F Systems with the F-block F_1oo2AI) in your safety program.
You can 󹪝nd more information in the programming and operating manual "SIMATIC Industrial
Software S7 F/FH Systems - Con󹪝guring and Programming (https://
support.industry.siemens.com/cs/ww/en/view/109773062)".
Applications of the F-I/O module
6.6 Application case 3: SIL3/Cat.4/PLe, 2- or 4-wire transducer, 1oo2
F-AI 8xI 2-/4-wire HART HA
50 Equipment Manual, 09/2021, A5E50557845-AA