RUGGEDCOM RX1500
Installation Guide
Chapter 6
Certification
EMC and Environmental Type Tests 51
Test Description Test Levels
Severity
Levels
Earth ground ports
Signal ports ± 2 kV Line-to-Ground,
± 2 kV Line-to-Line
4
DC Power Ports ± 2 kV Line-to-Ground,
± 1 kV Line-to-Line
3
IEC 61000-4-5 Surge
AC Power Ports ± 4 kV Line-to-Ground,
± 2 kV Line-to-Line
4
Signal ports
DC Power Ports
AC Power Ports
IEC 61000-4-6 Induced (Conducted) RFI
Earth ground ports
10 V 3
40 A/m, continuous,
1000 A/m for 1 s
Note
a
IEC 61000-4-8 Magnetic Field Enclosure Ports
1000 A/m for 1 s 5
DC Power Ports 30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
IEC 61000-4-29 Voltage Dips and Interrupts
AC Power Ports 30% for 1 period, 60% for 50 periods
IEC 61000-4-11 Voltage Dips and Interrupts AC Power Ports 100% for 5 periods,
100% for 50 periods
Signal ports
DC Power Ports
IEC 61000-4-12 Damped Oscillatory
AC Power Ports
2.5 kV common, 1 kV
differential mode @1 MHz
3
Signal portsIEC 61000-4-16 Mains Frequency Voltage
DC Power Ports
30 V Continuous, 300 V for 1 s 4
IEC 61000-4-17 Ripple on DC Power Supply DC Power Ports 10% 3
Signal ports 2 kV (Failsafe Relay output)
DC Power Ports 1.5 kV
Dielectric Strength
AC Power Ports 2 kV
Signal ports 5 kV (Failsafe Relay output)
DC Power Ports
IEC 60255-5
HV Impulse
AC Power Ports
5 kV
a
Siemens-specified severity levels
IEEE 1613 EMC Immunity Type Tests
NOTE
The RX1500 meets Class 2 requirements for an all-fiber configuration and Class 1 requirements for
copper ports.

Table of Contents

Other manuals for Siemens SIMATIC NET RUGGEDCOM RX1512

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET RUGGEDCOM RX1512 and is the answer not in the manual?

Siemens SIMATIC NET RUGGEDCOM RX1512 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET RUGGEDCOM RX1512
CategorySwitch
LanguageEnglish

Related product manuals