Configuration, programming
4.7 FTP communication
CP 1543-1
Operating Instructions, 12/2019, C79000-G8976-C289-08
55
Evaluating status codes
Note
Evaluation
Evaluation for BUSY = 0
Do not evaluate the status displays until BUSY = 0.
Status 8Fxx
H
For entries coded with status 8Fxx
H
, refer to the information in the STEP 7 Standard and
System Functions reference manual. The chapter describing error evaluation with the
RET_VAL output parameter contains detailed information.
Table 4- 9 FTP_CMD: Meaning of the STATUS parameter in conjunction with DONE and ERROR
DONE
ERROR
STATUS
Meaning
0
0
0000
H
No job is being executed.
1
0
0000
H
the job was completed without error.
0
0
7001
H
The job was initiated for the first time.
0
0
7002
H
Job still running.
0 1 80C4
H
Communication error (occurs temporarily, it is usually best to repeat
the job in the user program).
0
1
8183
H
The configuration does not match the job parameters.
0 1 8401
H
Unknown error
Possible causes:
A timeout was detected on the connection.
The FTP server has aborted the connection.
Remedy: Send the QUIT and CONNECT commands again to re-
establish the connection.
0 1 8402
H
The connection has an error status.
The timeout of the connection may have been exceeded or the FTP
server may have terminated the connection.
Remedy: Send the QUIT and CONNECT commands to re-establish the
connection.
0
1
8403
H
Login has failed.
0
1
8404
H
FTP server is not obtainable.
0
1
8405
H
Transfer has failed.
0
1
8406
H
Timeout for current action
0
1
8407
H
File was not found on the FTP server.
0
1
8408
H
Transfer not possible.
0
1
8409
H
File could not be fetched.
0
1
8410
H
Setting the TCP port for the data connection has failed.
0
1
8411
H
Offset information does not match.
0
1
8412
H
Error changing the specified directory
0
1
8413
H
Error receiving data

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET S7-1500 and is the answer not in the manual?

Siemens SIMATIC NET S7-1500 Specifications

General IconGeneral
Product FamilySIMATIC NET
Product SeriesS7-1500
Supply voltage24 V DC
Protection classIP20
TypeIndustrial Ethernet
Transfer rate10/100/1000 Mbps
ProtocolsPROFINET, TCP/IP
Operating temperature0 °C to 60 °C
Storage Temperature-40 °C to 70 °C
InterfaceRJ45
Product type designationSIMATIC NET S7-1500
Relative Humidity5 to 95% (non-condensing)

Related product manuals