Device CLASS 1 LASER Product
SCALANCE XM416-4C (*)
* In modular devices, you can nd the marking in the operating instructions for the plug-in transceiver
or extender used.
CAUTION
Use of controls or adjustments or performance of procedures other than those specied herein
may result in hazardous radiation exposure.
Mechanical stability (in operation)
Device IEC 60068-2-6 vibration * IEC 60068-2-6 vibration IEC 60068-2-27 shock
5 - 9 Hz: 3.5 mm
9 - 150 Hz: 1 g
1 octave/min, 20 sweeps
10 - 58 Hz: 0.075 mm
85 - 150 Hz: 1 g
1 octave/min, 20 sweeps
15 g, 11 ms duration
6 shocks per axis
SCALANCE XM408-4C ● ● ●
SCALANCE XM408-8C ● ● ●
SCALANCE XM416-4C ● ● ●
* Note: When installing on an S7-300 or S7-1500 standard rail
Installation guidelines
The devices meet the requirements if you adhere to the installation and safety instructions
contained in this documentation and in the following documentation when installing and
operating the devices.
• "Industrial Ethernet / PROFINET Industrial Ethernet" System Manual (
https://
support.industry.siemens.com/cs/ww/en/view/27069465)
• "Industrial Ethernet / PROFINET - Passive Network Components" System Manual (https://
support.industry.siemens.com/cs/ww/en/view/84922825)
• "EMC Installation Guidelines" conguration manual (https://
support.industry.siemens.com/cs/ww/en/view/60612658)
WARNING
Personal injury and property damage can occur
The installation of expansions that are not approved for SIMATIC NET products or their target
systems may violate the requirements and regulations for safety and electromagnetic
compatibility.
Only use expansions that are approved for the system.
Approvals
SCALANCE XM-400