Properties
1.1 Power module PM-E DC24V (6ES7138-4CA01-0AA0)
Power module PM-E DC24V (6ES7138-4CA01-0AA0)
10 Manual, 04/2007, A5E01119952-02
Technical data PM-E DC24V (6ES7138-4CA01-0AA0)
Dimensions and weight
Dimension B (mm)
15
Weight
Approx. 35 g
Voltages, currents, potentials
Rated load voltage
24 VDC
• Overvoltage protection
No
Protection with automatic circuit breakers
Yes, tripping characteristic B, C
Max. current-carrying capacity (up to 60°C)
10 A
• Short-circuit protection
No
Electrical isolation
• Between rated load voltage and backplane
bus
Yes
• Between the power modules
Yes
Insulation test voltage
500 VDC
Current consumption
• From the load voltage L+ (no load)
Max. 4 mA
Power dissipation of the module
Typically 100 mW
Parameter length
3 bytes
Status, interrupts, diagnostics
Diagnostic function
Yes
• Group error
Red "SF" LED
• Load voltage monitoring
Green "PWR" LED
• Diagnostic information readable
Yes