2 Engineering
Securely Connecting RTU3041C to TeleControl Server Basic
Entry ID: 109739240, V3.0, 07/2021
57
© Siemens AG
2021 All rights reserved
36. Add a new function block (FB1).
36
37. Select "GPS position" as the function.
38. Interconnect the parameters as follows:
Position: System location
Radius (m): 1000
Output: gpsPosition (DM2)
Distance: distance (AM2)
37
38
38
38
39. Add a new function block (FB2) below it.
39
40. Select "Send SMS" as the function.
41. Interconnect the parameters as follows:
Trigger: gpsPosition (DM2)
Send immediately: True
Recipient: Administrator SMS
Text: gpsPositionOK
40
41
41
42. Add a new function block (FB3) below.
42