Technical specifications
CPU 1512C-1 PN (6ES7512-1CK00-0AB0)
130 Manual, 09/2016, A5E35306440-AB
6ES7512-1CK00-0AB0
Number of hardware interrupt OBs
50
Number of DPV1 interrupt OBs
3
Number of isochronous mode OBs
1
Number of technology synchronization inte
rrupt
OBs
2
Number of startup OBs
100
Number of asynchronous error OBs
4
Number of synchronous error OBs
2
Number of diagnostics interrupt OBs
1
Nesting depth
per priority class
24
Counters, timers and their retentivity
S7 counters
Number
2048
Retentivity
can be set
Yes
IEC counters
Number
Any (only limited by the work memory)
Retentivity
can be set
Yes
S7 timers
Number
2048
Retentivity
can be set
Yes
IEC timers
Number
Any (only limited by the work memory)
Retentivity
can be set
Yes
Data areas and their retentivity
Retentive data area in total (incl. timers, counters,
bit memory), max.
128 KB; in total; for bit memory, timers, counters,
DBs and technological data (axes), usable reten-
tive memory: 88 KB
Bit memory
Number, max.
16 KB
Number of clock memory bits
8; there are 8 clock memory bits, grouped in one
clock memory byte
Data blocks
Retentivity can be set
Yes
Retentivity preset
No
Local data
per priority class, max.
64 KB; max. 16 KB per block
Address area
Number of IO modules
2048; max. number of modules/submodules