EasyManua.ls Logo

Siemens Simatic S7-300 - Page 37

Siemens Simatic S7-300
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation, connection, commissioning, removal
5.3 Installing and connecting up
CP 343-1 Lean
Equipment Manual, 01/2023, C79000−G8976−C198−09
37
WARNING
Open equipment
The devices are "open equipment" acc. to the standard IEC 61010-2-201 or UL 61010-2-201
/ CSA C22.2 No. 61010-2-201. To fulfill requirements for safe operation with regard to
mechanical stability, flame retardation, stability, and protection against contact, the
following alternative types of installation are specified:
Installation in a suitable cabinet.
Installation in a suitable enclosure.
Installation in a suitably equipped, enclosed control room.
WARNING
Power supply
The device is designed for operation with a directly connectable safety extra low voltage
(SELV) from a limited power source (LPS).
The power supply therefore needs to meet at least one of the following conditions:
Only safety extra low voltage (SELV) with limited power source (LPS) complying with IEC
60950-1 / EN 60950-1 / VDE 0805-1 or IEC 62368-1 / EN 62368-1 / VDE 62368-1 may be
connected to the power supply terminals.
The power supply unit for the device must meet NEC Class 2 according to the National
Electrical Code (r) (ANSI / NFPA 70).
If the equipment is connected to a redundant power supply (two separate power supplies),
both must meet these requirements.
Note
Pulling/plugging
Pulling/plugging the CP when the power is on is not permitted.
You should also remember that by removing a module from the rack, all modules on the
other side of it will be disconnected from the CPU.

Table of Contents

Other manuals for Siemens Simatic S7-300

Related product manuals