10.99 Faults and Alarms
Siemens AG 6SE7087-6KP50
SIMOVERT MASTERDRIVES Operating Instructions 12-9
Number / Fault Cause Counter-measure
F099
Friction characteristic
record
Recording of the friction characteristic was
interrupted or not done at all.
Fault value r949 gives the cause (bit coded):
Bit Meaning Value displayed
0 Pos. speed limit 1
1 Neg. speed limit 2
2 Releases missing: 4
direction of rotation, inverter, controller
3 Speed controller connecting 8
4 Interrupt through cancellation of the 16
record command
5 Illegal dataset changover 32
6 Time exceeded 64
7 Measuring error 128
F109
Mld R(L)
The rotor resistance determined during
measurement of the direct current deviates too
greatly.
F111
MId DSP
A fault has occurred during the Mot Id.
F112
Mid X(L)
A fault has occurred during measurement of
the motor inductances or leakages.
F114
MId OFF
The converter has automatically stopped the
automatic measurement due to the time limit
up to power-up having been exceeded or due
to an OFF command during the measurement,
and has reset the function selection in P115.
Re-start with P115 function selection = 2
"Motor identification at standstill".The ON
command must be given within 20 sec. after
the alarm message A078 = standstill
measurement has appeared.
Cancel the OFF command and re-start
measurement.
F116
Technology board fault
not Compact PLUS
See TB documentation See TB documentation
F117
Technology board fault
See TB documentation See TB documentation
F118
Technology board fault
not Compact PLUS
See TB documentation See TB documentation
F119
Technology board fault
not Compact PLUS
See TB documentation See TB documentation
F120
Technology board fault
not Compact PLUS
See TB documentation See TB documentation
F121
Technology board fault
not Compact PLUS
See TB documentation See TB documentation
F122
Technology board fault
not Compact PLUS
See TB documentation See TB documentation
F123
Technology board fault
not Compact PLUS
See TB documentation See TB documentation