10.99 Faults and Alarms
Siemens AG 6SE7087-6KP50
SIMOVERT MASTERDRIVES Operating Instructions 12-15
Number / Alarm Cause Counter-measure
A034
Setpoint/actual value
deviation
Bit 8 in r552 status word 1 of the setpoint
channel. The difference between freqeuncy
setpoint/actual value is greater than the
parameterized value and the control
monitoring time has elapsed.
Check
- whether an excessive torque requirement is
present
- whether the motor has been dimensioned too
small.
Increase values P792 Perm Deviation Frq/
set/actual DevSpeed and P794 Deviation Time
A036
Brake checkback
"Brake still closed"
The brake checkback indicates the "Brake still
closed" state.
Check brake checkback (see FD 470)
A037
Brake checkback
"Brake still open"
The brake checkback indicates the "Brake still
open" state.
Check brake checkback (see FD 470)
A042
Motor stall/block
Motor is stalled or blocked.
The alarm cannot be influenced by P805
"PullOut/BlckTime", but by P794 "Deviation
Time"
Check
- whether the drive is blocked
- Whether the drive has stalled
A049
No slave
not Compact PLUS
At serial I/O (SCB1 with SCI1/2), no slave is
connected or fiber-optic cable is interrupted or
slaves are without voltage.
P690 SSCI AnaIn Conf
- Check slave.
- Check cable.
A050
Slave incorrect
not Compact PLUS
At ser. I/O the slaves required according to a
parameterized configuration are not present
(slave number or slave type): Analog inputs or
outputs or digital inputs or outputs have been
parameterized which are not physically
present.
Check parameter P693 (analog outputs), P698
(digital outputs). Check connectors
K4101...K4103, K4201...K4203 (analog inputs)
and binectors B4100...B4115, B4120...B4135,
B4200...B4215, B4220...B4235 (digital inputs)
for connecting.
A051
Peer baud rate
not Compact PLUS
In a peer-to-peer connection a baud rate has
been selected which is too high or too
different.
Adjust the baud rate in conjunction with the
SCB boards P701 SCom/SCB Baud Rate
A052
Peer PcD L
not Compact PLUS
In a peer-to-peer connection, a PcD length has
been set which is too high (>5).
Reduce number of words P703 SCom/SCB
PcD #
A053
Peer Lng f.
not Compact PLUS
In a peer-to-peer connection, the pcD length of
transmitter and receiver do not match.
Adjust the word length for transmitter and
receiver
P703 SCom/SCB PcD #
A057
TB Param
not Compact PLUS
Occurs when a TB is logged on and present,
but parameter tasks from the PMU, SCom1 or
SCom2 have not been answered by the TB
within 6 seconds.
Replace TB configuration (software)
A061
Alarm 1
Function blocks
An active signal is present at binector U065
(1).
Check cause of alarm (see FD 710)
A062
Alarm 2
Function blocks
An active signal is present at binector U066
(1).
Check cause of alarm (see FD 710)
A063
Alarm 3
Function blocks
An active signal is present at binector U067
(1).
Check cause of alarm (see FD 710)

Other manuals for Siemens simovert masterdrives

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simovert masterdrives and is the answer not in the manual?

Siemens simovert masterdrives Specifications

General IconGeneral
BrandSiemens
Modelsimovert masterdrives
CategoryDC Drives
LanguageEnglish

Related product manuals