EasyManua.ls Logo

Siemens SINAMICS S150 - Functions, monitoring, and protective functions

Siemens SINAMICS S150
530 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130
Engineering Information
SINAMICS Engineering Manual – November 2015
Ó Siemens AG
301/528
SINAMICS G130 Maximum permissible motor cable length
Line supply voltage Rated power at
400 V / 500 V / 690 V
Shielded cable
e.g. Protodur NYCWY
Unshielded cable
e.g. Protodur NYY
With one motor reactor
380 V – 480 V 3AC 110 kW - 560 kW 300 m 450 m
500 V – 600 V 3AC 110 kW - 560 kW 300 m 450 m
660 V – 690 V 3AC 75 kW - 800 kW 300 m 450 m
With dv/dt filter plus VPL
380 V – 480 V 3AC 110 kW - 560 kW 300 m 450 m
500 V – 600 V 3AC 110 kW - 560 kW 300 m 450 m
660 V – 690 V 3AC 75 kW - 800 kW 300 m 450 m
With dv/dt filter compact plus VPL
380 V – 480 V 3AC 110 kW - 560 kW 100 m 150 m
500 V – 600 V 3AC 110 kW - 560 kW 100 m 150 m
660 V – 690 V 3AC 75 kW - 800 kW 100 m 150 m
With sine-wave filter
380 V – 480 V 3AC 110 kW - 250 kW 300 m 450 m
500 V – 600 V 3AC 110 kW - 132 kW 300 m 450 m
Permissible motor cable lengths for SINAMICS G130 (continued)
When two motor reactors are connected in series, the permissible cable lengths can be increased even further to
450 m with shielded cables and 675 m with unshielded cables.