SINAMICS G130
Engineering Information
SINAMICS Engineering Manual – November 2015
Ó Siemens AG
301/528
SINAMICS G130 Maximum permissible motor cable length
Line supply voltage Rated power at
400 V / 500 V / 690 V
Shielded cable
e.g. Protodur NYCWY
Unshielded cable
e.g. Protodur NYY
With one motor reactor
380 V – 480 V 3AC 110 kW - 560 kW 300 m 450 m
500 V – 600 V 3AC 110 kW - 560 kW 300 m 450 m
660 V – 690 V 3AC 75 kW - 800 kW 300 m 450 m
With dv/dt filter plus VPL
380 V – 480 V 3AC 110 kW - 560 kW 300 m 450 m
500 V – 600 V 3AC 110 kW - 560 kW 300 m 450 m
660 V – 690 V 3AC 75 kW - 800 kW 300 m 450 m
With dv/dt filter compact plus VPL
380 V – 480 V 3AC 110 kW - 560 kW 100 m 150 m
500 V – 600 V 3AC 110 kW - 560 kW 100 m 150 m
660 V – 690 V 3AC 75 kW - 800 kW 100 m 150 m
With sine-wave filter
380 V – 480 V 3AC 110 kW - 250 kW 300 m 450 m
500 V – 600 V 3AC 110 kW - 132 kW 300 m 450 m
Permissible motor cable lengths for SINAMICS G130 (continued)
When two motor reactors are connected in series, the permissible cable lengths can be increased even further to
450 m with shielded cables and 675 m with unshielded cables.