The following table specifies the rms values of the line currents which occur at the beginning of the precharging
process in the case of line supply voltages 400 V or 690 V. Where other line voltage values apply, the values must be
converted in proportion to the line voltage.
The specified precharging currents decay in accordance with an e-function until the precharging process is
completed after a period of typically 1 to 2 s. Due to the temperature rise in the precharging resistors during the
process, the minimum permissible interval for complete precharging of the DC link is 3 minutes.
Power rating of S150
at
400 V or 690 V
[kW]
Rated output
current
[A]
Line current at the beginning of DC link
precharging (initial rms value)
at 400 V or 690 V
[A]
380 V – 480 V 3AC
110 kW 210 A 29 A
132 kW 260 A 29 A
160 kW 310 A 59 A
200 kW 380 A 59 A
250 kW 490 A 59 A
315 kW 605 A 91 A
400 kW 745 A 91 A
450 kW 840 A 91 A
560 kW 985 A 182 A
710 kW 1260 A 182 A
800 kW 1405 A 182 A
500 V – 690 V 3AC
75 kW 85 A 29 A
90 kW 100 A 29 A
110 kW 120 A 29 A
132 kW 150 A 29 A
160 kW 175 A 58 A
200 kW 215 A 58 A
250 kW 260 A 58 A
315 kW 330 A 58 A
400 kW 410 A 86 A
450 kW 465 A 86 A
560 kW 575 A 86 A
710 kW 735 A 172 A
800 kW 810 A 172 A
900 kW 910 A 172 A
1000 kW 1025 A 172 A
1200 kW 1270 A 172 A
SINAMICS S150 converter cabinet units: Line currents at the beginning of precharging (initial rms values)
8.6 Load side components
8.6.1 Line fuses
The use of combined fuses (3NE1..., class gS) is recommended in order to limit the extent of damage in the event of
a serious component defect in the converter. These fuses have the following properties:
· Quick-acting
· Low arc voltage
· Effective current limiting.