Pump switch-in/switch-out
SINAMICS V20 multi-pump control
12 Operating Manual, 05/2018, A5E43416874-002
If the pump controlled by the inverter runs at a speed lower than the frequency switch-out
threshold (P4014 + P1080) and the PID error is lower than the PID error switch-out threshold
(-P2373) for specified time (P2375), the inverter first switches off the pump (OFF2) which
runs in inverter operation, and then captures a running pump and switches it from line
system operation to inverter operation. Parameter P4012 is used to control the selection
mode for switching in/out motors.
● P4012 = 0: Selecting the next pump according to the fixed sequence. The inverter
switches out the pump by following the sequence M4, M3, M2, to M1.
● P4012 = 1: Selecting the next pump according to the operating hours. The inverter first
switches out the pump with the most absolute operating hours (r4026 to r4029).