Service mode
SINAMICS V20 multi-pump control
26 Operating Manual, 05/2018, A5E43416874-002
Parameter
Function
Setting
P0732[0...2] BI: Function of digital output 2 Defines source of digital output 2.
Range: 0 to 4294967295 (default setting: 4000.2)
P0733[0...2] BI: Function of digital output 3 Defines source of digital output 3.
Range: 0 to 4294967295 (default setting: 4000.3)
P0734[0...2] BI: Function of digital output 4 Defines source of digital output 4.
Range: 0 to 4294967295 (default setting: 4000.4)
r4000 Multi-pump control status word This parameter defines the bitwise status word for the multi-
pump control function.
Bit 00: ON/OFF1 (output to P0840)
Bit 01: Motor 1 switching on (output to P0731)
Bit 02: Motor 2 switching on (output to P0732)
Bit 03: Motor 3 switching on (output to P0733)
Bit 04: Motor 4 switching on (output to P0734)
Bit 05: Switching-in/-out operation in progress
Bit 06: No idle motor is running
Bit 07: OFF2 (output to P0845)
P4016 Multi-pump control service mode: motor 1 This parameter controls the service mode of motor 1.
= 0: Motor 1 service mode is disabled
= 1: Motor 1 service mode is enabled by DI1 high level
= 2: Motor 1 service mode is enabled by DI2 high level
= 3: Motor 1 service mode is enabled by DI3 high level
= 4: Motor 1 service mode is enabled by DI4 high level
= 5: Motor 1 service mode is enabled by DI5 high level
= 6: Motor 1 service mode is enabled by DI6 high level
= 7: Motor 1 service mode is enabled
Range: 0 to 7 (default setting: 0)
P4017 Multi-pump control service mode: motor 2 This parameter controls the service mode of motor 2. Refer to
P4016.
P4018 Multi-pump control service mode: motor 3 This parameter controls the service mode of motor 3. Refer to
P4016.
P4019 Multi-pump control service mode: motor 4 This parameter controls the service mode of motor 4. Refer to
P4016.
r4062 Inverter-controlled motor number This parameter displays which motor is controlled by the invert-