411101 Impermissible Parameter Axis in FB11
Definitions: Axis parameter not within the permissible range.
Reaction: Alarm display.
Remedy: Use permissible axis number.
Program
Continuation:
Internal
411501 Incorrect version of FB 15, > general reset, do not transmit FB 15 from
project
Definitions: FB 15 does not match the basic program used.
Reaction: Alarm display.
Remedy: General PLC reset. Use correct version of the basic program.
Program
Continuation:
Internal
411502 Incorrect basic PLC program version
Definitions: FB 15 does not match the basic program used.
Reaction: Alarm display.
Remedy: Load the basic program that matches the NCK version.
Program
Continuation:
Internal
428201 Diagnostic alarm
Definitions: OB82 or OB86 has been triggered.
Reaction: Alarm display.
Remedy: Rectify the cause of the error displayed
Program
Continuation:
Switch control OFF - ON.
428221 Diagnostic alarm from diagnostics address %Z
Definitions: OB82 or OB86 has been triggered.
Reaction: Alarm display.
Remedy: Rectify the cause of the error displayed
Program
Continuation:
Switch control OFF - ON.
428601 Module failure of the expansion unit
Definitions: OB82 or OB86 has been triggered.
Reaction: Alarm display.
Remedy: Rectify the cause of the error displayed
Program
Continuation:
Switch control OFF - ON.
428602 Recurrence of module failure of the expansion unit
Definitions: OB82 or OB86 has been triggered.
Reaction: Alarm display.
Remedy: Rectify the cause of the error displayed
Program
Continuation:
Switch control OFF - ON.