2 Installation
2.2 Electrical Connection
2.2.3 Wiring of the Option Modules
Manual
118
SIP ART DR24 6DR2410
C79000-G7476-C153-03
D 6DR2800-8V universal module for analog input
The universal module can be plugged into slot 2 (analog input AE4) and slot 3 (analog input
AE5). The measuring ranges are set using the menu CAE4/CAE5.
- Pin assignment for mV transmitter
Direct input U
max = ±175 mV
R
L4
R
L1
R
L1
+R
L4
≤1kΩ
+
--
mV
Block diagram of the mV module 6DR2800-8V
i
m
U
+REF
+
--
A
D
Sensor
6DR2800-8V
4
3
2
1
Figure 2-16 Wiring of UNI module
- Pin assignment measuring range plug 6DR2805-8J for U or I
89k1
200R
8k95
50R
1k
10 V
+
--
SMART
20 mA
+
--
perm. common mode
voltage 50 V UC
U
H
+
--
Measuring range plug 6DR2805-8J
Block diagram of mV module 6DR2800-8V
i
m
U
+REF
+
--
A
D
Sensor
6DR2800-8V
4
3
2
1
+
--
10 V 20 mA
4L
20 mA
2L
SMART
--
L+
CND
L
4
3
2
1
Figure 2-17 Wiring of UNI module